• Tell us some more • Upload in Progress • Upload failed. Please upload a file larger than 100x100 pixels • We are experiencing some problems, please try again. • You can only upload files of type PNG, JPG, or JPEG.
Download Utility RUPS 2000 for UPS Monitoring for Windows 2000, Windows XP (32bit), Windows Vista (32bit), DOS, Linux. Free download driver (utilities) for Sven Uninterruptible Power Supply (UPS) Power Pro+ 500 (v.2) direct links.
• You can only upload files of type 3GP, 3GPP, MP4, MOV, AVI, MPG, MPEG, or RM. • You can only upload photos smaller than 5 MB.
• You can only upload videos smaller than 600MB. • You can only upload a photo (png, jpg, jpeg) or a video (3gp, 3gpp, mp4, mov, avi, mpg, mpeg, rm). • You can only upload a photo or a video. • Video should be smaller than 600mb/5 minutes • Photo should be smaller than 5mb • You can only upload a photo.
• • • • • • • • • • • Do you have any information on UPS battery maintenance and storage? Can the UPS battery be replaced? Yes, all Acumentrics UPS units have user-replaceable batteries. If you require a new battery pack, please email the UPS (uninterruptible power supply) model number and your request to. A quote will be sent to you for the appropriate battery pack. If you would just like the battery cells replaced, please email the UPS model number and the serial number of the battery pack to:; request a return authorization number and the cost for the repair.
For battery maintenance and storage information, please read the following: For the ACG2500 Series UPS: Maintenance and Battery Storage The proper storage of UPS batteries cannot be overemphasized. Improper battery storage is the most common form of battery misuse. All batteries exhibit a loss of charge over time even when stored in an open circuit condition. This is called self-discharge.
Facerig free download mac. Both chemical and electrochemical reactions within the battery cause this consumption of the stored energy. The self-discharge reaction rate increases as a function of temperature. If the batteries are stored long enough without a periodic replenishment of charge, an irreversible loss of battery capacity can occur, causing premature battery failure. All Acumentrics battery packs are shipped fully charged. They should be stored separately from the uninterruptible power supply and used on a FIFO (First In, First Out) basis. All battery packs should be recharged before use of the UPS (uninterruptible power supply) if 100% capacity is required.
The stored battery packs should be kept on a maintenance program and should be recharged periodically according to the recommendations shown in table 1. Battery packs can be recharged using the UPS (uninterruptible power supply). Table 1: Storage Temperature and Supplementary Recharge Intervals The battery OCV (Open Circuit Voltage) can be used as an indicator of battery pack residual capacity. When measuring the OCV, the battery pack should not have been charged or discharged within the past 24 hours. A supplemental recharge should be performed if the battery pack OCV is 24.6 volts or less when measured at 25ºC (77ºF).
The ACG26BP has a recharge time of 2-hours to 90% present capacity from full discharge. The ACG2500BP has a 4-hour recharge time to 90% present capacity from full discharge. Charging the UPS Battery The UPS (uninterruptible power supply) charges its battery when connected to utility power. For best results, charge the battery 4-hours before use of the UPS. It is acceptable to use the UPS (uninterruptible power supply) without first charging the battery, but battery run time may be shorter until the battery fully charges The UPS is continually creating the AC output from a high voltage DC bus, thus protecting your equipment from surges, spikes, brownouts, blackouts and noise. This unit is an on-line Power Factor Corrected (PFC), Uninterruptible Power Supply (UPS). This UPS accepts wide range voltage and frequency inputs to allow it to provide clean, reliable AC power to the equipment it supports.
General Maintenance: Inspection Ensure the unit is clean with no fluid spills. Do not store anything on the unit.
Cleaning The 2000 Watt Rugged-UPS ™ product and its accessories are chemically resistant to most common cleaning solutions and non-caustic detergents. The following list includes approved cleaning solutions: • 90% Isopropyl alcohol • Soap and water • Chlorine bleach (30ml/water) Acumentrics recommends cleaning the UPS unit and cables with a soft damp cloth, and cleaning agents mentioned.
Do NOT immerse any part of the UPS unit in water. Do not use ketones (MEK, acetone, etc). Avoid using abrasives (e.g., paper towels) on the UPS. For the ACG1250 Series UPS: Storage and Maintenance of UPS Battery Packs Overview Proper maintenance and storage is required for lead acid batteries in order to extend the useful life of the battery and prevent potential damage to the UPS (uninterruptible power supply). Under normal operation, battery maintenance is not required other than periodic checks of the charge status. However, the proper storage of batteries cannot be overemphasized. Improper battery storage is the most common form of battery misuse.
• Tell us some more • Upload in Progress • Upload failed. Please upload a file larger than 100x100 pixels • We are experiencing some problems, please try again. • You can only upload files of type PNG, JPG, or JPEG.
Download Utility RUPS 2000 for UPS Monitoring for Windows 2000, Windows XP (32bit), Windows Vista (32bit), DOS, Linux. Free download driver (utilities) for Sven Uninterruptible Power Supply (UPS) Power Pro+ 500 (v.2) direct links.
• You can only upload files of type 3GP, 3GPP, MP4, MOV, AVI, MPG, MPEG, or RM. • You can only upload photos smaller than 5 MB.
• You can only upload videos smaller than 600MB. • You can only upload a photo (png, jpg, jpeg) or a video (3gp, 3gpp, mp4, mov, avi, mpg, mpeg, rm). • You can only upload a photo or a video. • Video should be smaller than 600mb/5 minutes • Photo should be smaller than 5mb • You can only upload a photo.
• • • • • • • • • • • Do you have any information on UPS battery maintenance and storage? Can the UPS battery be replaced? Yes, all Acumentrics UPS units have user-replaceable batteries. If you require a new battery pack, please email the UPS (uninterruptible power supply) model number and your request to. A quote will be sent to you for the appropriate battery pack. If you would just like the battery cells replaced, please email the UPS model number and the serial number of the battery pack to:; request a return authorization number and the cost for the repair.
For battery maintenance and storage information, please read the following: For the ACG2500 Series UPS: Maintenance and Battery Storage The proper storage of UPS batteries cannot be overemphasized. Improper battery storage is the most common form of battery misuse. All batteries exhibit a loss of charge over time even when stored in an open circuit condition. This is called self-discharge.
Facerig free download mac. Both chemical and electrochemical reactions within the battery cause this consumption of the stored energy. The self-discharge reaction rate increases as a function of temperature. If the batteries are stored long enough without a periodic replenishment of charge, an irreversible loss of battery capacity can occur, causing premature battery failure. All Acumentrics battery packs are shipped fully charged. They should be stored separately from the uninterruptible power supply and used on a FIFO (First In, First Out) basis. All battery packs should be recharged before use of the UPS (uninterruptible power supply) if 100% capacity is required.
The stored battery packs should be kept on a maintenance program and should be recharged periodically according to the recommendations shown in table 1. Battery packs can be recharged using the UPS (uninterruptible power supply). Table 1: Storage Temperature and Supplementary Recharge Intervals The battery OCV (Open Circuit Voltage) can be used as an indicator of battery pack residual capacity. When measuring the OCV, the battery pack should not have been charged or discharged within the past 24 hours. A supplemental recharge should be performed if the battery pack OCV is 24.6 volts or less when measured at 25ºC (77ºF).
The ACG26BP has a recharge time of 2-hours to 90% present capacity from full discharge. The ACG2500BP has a 4-hour recharge time to 90% present capacity from full discharge. Charging the UPS Battery The UPS (uninterruptible power supply) charges its battery when connected to utility power. For best results, charge the battery 4-hours before use of the UPS. It is acceptable to use the UPS (uninterruptible power supply) without first charging the battery, but battery run time may be shorter until the battery fully charges The UPS is continually creating the AC output from a high voltage DC bus, thus protecting your equipment from surges, spikes, brownouts, blackouts and noise. This unit is an on-line Power Factor Corrected (PFC), Uninterruptible Power Supply (UPS). This UPS accepts wide range voltage and frequency inputs to allow it to provide clean, reliable AC power to the equipment it supports.
General Maintenance: Inspection Ensure the unit is clean with no fluid spills. Do not store anything on the unit.
Cleaning The 2000 Watt Rugged-UPS ™ product and its accessories are chemically resistant to most common cleaning solutions and non-caustic detergents. The following list includes approved cleaning solutions: • 90% Isopropyl alcohol • Soap and water • Chlorine bleach (30ml/water) Acumentrics recommends cleaning the UPS unit and cables with a soft damp cloth, and cleaning agents mentioned.
Do NOT immerse any part of the UPS unit in water. Do not use ketones (MEK, acetone, etc). Avoid using abrasives (e.g., paper towels) on the UPS. For the ACG1250 Series UPS: Storage and Maintenance of UPS Battery Packs Overview Proper maintenance and storage is required for lead acid batteries in order to extend the useful life of the battery and prevent potential damage to the UPS (uninterruptible power supply). Under normal operation, battery maintenance is not required other than periodic checks of the charge status. However, the proper storage of batteries cannot be overemphasized. Improper battery storage is the most common form of battery misuse.